Building components- external wall - awmoho01a
 
 


Cross-section of standard configuration
[Additional views]

note:
When using cross laminated timber:
Variation 02-03: d ≥ 94,0; at least 3-layers, top layer at least 30mm; variation 00-01: d ≥ 78,0; at least 3-layers, top layer at least 25mm


Last update23.08.2017/hfa.plb
external wall: solid wood construction, not ventilated, without dry lining, with cladding

register of building materials used for this application, cross-section
(from outside to inside, dimensions in mm)

  Thickness Building material  λ   μ min - max   ρ   c  Reaction to fire
EN
 20.0 larch wood external wall cladding  0,155  50  600  1,600   D
 30.0 spruce wood battens (30/60)  0,120  50  450  1,600   D
  vapour-permeable membrane sd ≤ 0,3m           
*   spruce wood battens (40/50 or 80/60;e=625)  0,120  50  450  1,600   D
*   Insulation material            
*   Insulation material            
*   solid wood (e.g. cross laminated timber)  0,130  50  500  1,600   D
*   Exchangeable layer          
   
               
  Variations of building components

No. Thickness of layer Note Fire performance Thermal performance Acoustic performance Eco Sustainability Mass HTMLPDF
  D* E* F* G* H* Σ   REI U [W/(m²K)] mw,B,A [kg/m²] Diffusion Ln,w(Cl) Rw(C,Ctr) OI3Kon m [kg/m²]   
00   50,0  50,0  80,0  78,0  13,0  270,5  null
H=gypsum fibre board 
60  0,25  44,8  adequate  –  51(-3,-9)  -2,6  69,0   awmoho01a-00  
E/F = mineral wool [0,040; R≥ 70]
01   80,0  80,0  80,0  78,0  13,0  300,5  null
H=gypsum fibre board 
60  0,22  44,9  adequate  –  51(-3,-9)  1,6  72,4   awmoho01a-01  
E/F = mineral wool [0,040; R≥ 70]
02   50,0  50,0  80,0  94,0    274,0  without gypsum board lining
 
60  0,25  39,5  adequate  –  47(,)  -5,7  59,0   awmoho01a-02  
E/F = mineral wool [0,040; R≥ 70]
03   80,0  80,0  80,0  94,0    304,0  without gypsum board lining
 
60  0,21  39,6  adequate  –  47(,)  -1,5  62,4   awmoho01a-03  
E/F = mineral wool [0,040; R≥ 70]