Building components- external wall - awmopi04a
 
 


Cross-section of standard configuration
[Additional views]

Last update23.03.2017/hfa.plb
external wall: solid wood construction, not ventilated, with dry lining, with rendering

register of building materials used for this application, cross-section
(from outside to inside, dimensions in mm)

  Thickness Building material  λ   μ min - max   ρ   c  Reaction to fire
EN
 4.0 plaster   1,000  10 - 35  2000  1,130   A1
 60.0 mineral wool MW-PT [040; 155]   0,040  155  1,030   A1
 15.0 fibreboard (MDF)   0,120  11  600  1,700   D
 300.0 Light composite wood-based beams (I-beams) with solid wood flanges (60/45) and hard board intermediate web (≥ 6,7) e=625  0,400  20 - 30  800  1,700   D
*   Insulation material            
*   cross laminated timber d ≥ 94,0; at least 3-layers, top layer at least 30mm;  0,130  50  500  1,600   D
 80.0 spruce wood   0,120  50  450  1,600   D
*   Insulation material            
 12.5 gypsum plasterboards with improved properties at high temperatures (fire) or  0,250  10  800  1,050   A2
 12.5 gypsum fibre board   0,320  21  1000  1,100   A2
   
               
  Variations of building components

No. Thickness of layer Note Fire performance Thermal performance Acoustic performance Eco Sustainability Mass HTMLPDF
  F* Σ   REI U [W/(m²K)] mw,B,A [kg/m²] Diffusion Ln,w(Cl) Rw(C,Ctr) OI3Kon m [kg/m²]   
00   94,0  565,5    90  0,09  14,2  adequate  –  49(,)  39,0  110,8   awmopi04a-00  
E/H = cellulose fibre [040; 50]
01   94,0  565,5    90  0,09  14,1  adequate  –  49(,)  40,8  109,0   awmopi04a-01  
E/H = Wood fibre insulation [039; 45]
02   94,0  565,5    90  0,08  13,7  adequate  –  47(,)  52,5  99,2   awmopi04a-02  
E/H = glass wool [0,034; R=18]