Building components- external wall - awmopo02a Source: Saint-Gobain Rigips Austria GesmbH
 
 


Cross-section of standard configuration
[Additional views]

Last update28.09.2017/hfa.plb
external wall: solid wood construction, not ventilated, without dry lining, with rendering

register of building materials used for this application, cross-section
(from outside to inside, dimensions in mm)

  Thickness Building material  λ   μ min - max   ρ   c  Reaction to fire
EN
 6.0 plaster   1,000  10 - 35  2000  1,130   A1
 60.0 softboard [046; 200]   0,046  3 - 7  200  2,100   E
 160.0 finger-jointed solid construction timber (60/160; e=625)  0,120  50  450  1,600   D
 160.0 mineral wool [035; 18]   0,035  18  1,030   A1
*   cross laminated timber BBS 3 layer  0,130  50  470  1,600   D
*   gypsum plasterboards Rigips RF or  0,250  10  900  1,050   A2
  gypsum fibre board Rigidur H   0,350  19  1200  1,100   A1
   
               
  Variations of building components

No. Thickness of layer Note Fire performance Thermal performance Acoustic performance Eco Sustainability Mass HTMLPDF
  E* F* Σ   REI U [W/(m²K)] mw,B,A [kg/m²] Diffusion Ln,w(Cl) Rw(C,Ctr) OI3Kon m [kg/m²]   
00   90,0  15,0  331,0  BBS 3 layer
 
60  0,17  44,2  adequate  –  45(-2,-8)  5,3  90,1   awmopo02a-00  
 
01   90,0  0,0  316,0  BBS 3 layer; without gypsum board lining
 
30  0,17  38,7  adequate  –  45(-2,-8)  2,2  76,6   awmopo02a-01  
 
02   100,0  15,0  341,0  BBS 5 layer
 
90  0,16  44,0  adequate  –  45(-2,-8)  5,3  103,8   awmopo02a-02