Building components- external wall - awropi21a Source: Knauf Insulation GmbH
 
 


Cross-section of standard configuration
[Additional views]

Last update02.03.2017/hfa.plb
external wall: timber frame construction, not ventilated, with dry lining, with rendering

register of building materials used for this application, cross-section
(from outside to inside, dimensions in mm)

  Thickness Building material  λ   μ min - max   ρ   c  Reaction to fire
EN
 10.0 plaster   1,000  10 - 35  2000  1,130   A1
 25.0 Heraklith BM   0,090  2 - 5  370  2,000   B
 16.0 particleboard P5  0,130  50 - 100  700  1,700   D
*   finger-jointed solid construction timber (60/..; e=625)  0,120  50  450  1,600   D
*   Insulation material            
  vapour barrier sd≥ 9m       1000     
 50.0 Heraklith BM   0,090  2 - 5  370  2,000   B
 15.0 gypsum plasterboards with improved properties at high temperatures (fire)   0,250  10  800  1,050   A2
   
               
  Variations of building components

No. Thickness of layer Note Fire performance Thermal performance Acoustic performance Eco Sustainability Mass HTMLPDF
  D* E* Σ   REI U [W/(m²K)] mw,B,A [kg/m²] Diffusion Ln,w(Cl) Rw(C,Ctr) OI3Kon m [kg/m²]   
00   160,0  160,0  276,0    60  0,22  36,3  adequate  –  51(-4,-12)  11,9  82,2   awropi21a-00  
E = Heralan KP
01   120,0  120,0  236,0    60  0,27  35,9  adequate  –  48(-5,-13)  8,9  79,0   awropi21a-01  
E = Heralan KP
02   200,0  200,0  316,0    60  0,19  36,5  adequate  –  52(-3,-12)  15,0  85,3   awropi21a-02  
E = Heralan KP
03   240,0  240,0  356,0    60  0,16  36,7  adequate  –  53(-3,-11)  18,0  88,4   awropi21a-03  
E = Heralan KP