Building components- compartment wall - twmxxo03a
 
 


Cross-section of standard configuration
[Additional views]

note:
Cross laminated timer
Var. 00-01: thickness ≥ 78mm; 3-ply at least, surface layer at least 25mm
Var. 02: thickness ≥ 94,0mm; 3-ply at least, surface layer at least 30mm


Last update22.06.2017/hfa.plb
compartment wall: solid wood construction, without dry lining, double-layer

register of building materials used for this application, cross-section
(from outside to inside, dimensions in mm)

  Thickness Building material  λ   μ min - max   ρ   c  Reaction to fire
EN
*   Exchangeable layer          
*   solid wood (e.g. cross laminated timber)  0,130  50  500  1,600   D
*   impact sound absorbing subflooring MW-T   0,035  68  1,030   A1
*   solid wood (e.g. cross laminated timber)  0,130  50  500  1,600   D
*   Exchangeable layer          
   
               
  Variations of building components

No. Thickness of layer Note Fire performance Thermal performance Acoustic performance Eco Sustainability Mass HTMLPDF
  A* B* C* D* E* Σ   REI U [W/(m²K)] mw,B,A [kg/m²] Diffusion Ln,w(Cl) Rw(C,Ctr) OI3Kon m [kg/m²]   
00   12,5  78,0  30,0  78,0  12,5  211,0  A/E=gypsum plasterboards with improved properties at high temperatures (fire)/Gypsum fibre board  60  0,38  43,6  adequate  –  56(,)  -8,6  119,5   twmxxo03a-00  
 
01   12,5  78,0  60,0  78,0  12,5  241,0  C=2x30 mm, A/E=12,5
A/E=gypsum plasterboards with improved properties at high temperatures (fire)/Gypsum fibre board 
60  0,29  44,4  adequate  –  60(,)  -0,1  121,6   twmxxo03a-01  
 
02     94,0  30,0  94,0    218,0  A/E= without gypsum board lining
 
60  0,39  38,1  adequate  –  48(,)  -6,2  97,0   twmxxo03a-02